Arcanum Technical Director, Lawrie Abercrombie, digs into the recent breach across French supermarkets to explain what happened and why this story should concern us all beyond spoiled food and customer inconvenience.
Last weekend, hundreds of supermarkets in France found their refrigeration and freezer units running hot. Food was spoiled in bulk and there were reports of fires. It’s being described as unprecedented and it deserves attention well beyond retail.
What we know so far is that France’s national cyber agency, ANSSI, through CERT-FR, issued an alert on 12 October about “numerous compromises” of Danfoss AK-SM and AK-SC series refrigeration controllers. Danfoss says most of the affected units are old models that no longer receive updates, namely the AK-SM 800 (end of life since 2021) and the AK-SC 355 (phased out in 2016). Some current AK-SM 800A units were also hit, reportedly running outdated firmware.
What we don’t know is just as important. No one has said publicly how the attackers got in and no one has claimed or been blamed for the attack. The reporting I’ve seen doesn’t say default passwords were involved. CERT-FR’s own wording is that exposing a management interface to the internet is contrary to best practice. Internet scans find a large number of exposed Danfoss controllers, with France holding most of those detected. These facts are consistent, but nobody has yet confirmed they are linked.
Earlier this year, Claroty’s research team found flaws in the AK-SM 800A, including an authentication bypass based on a hidden date-derived code. Danfoss has patched these and no one has tied them to this attack.
This isn’t a one-off. The attack fits a pattern that UK and US agencies have been warning about all year:
- In August, the NCSC warned of increased targeting of operational technology by multiple threat actors, causing “some limited real-world disruption”. Its message was that organisations should not assume their OT is inaccessible from the internet without verifying it.
- A joint US advisory (FBI, CISA, NSA and others), updated in July, describes attackers scanning for internet-exposed PLCs in water, energy and government facilities. They connected using legitimate engineering software and, in some cases, altered operator displays so staff couldn’t see anything was wrong. Unlike earlier campaigns, no default passwords or software vulnerabilities were needed. The enablers were weak segmentation and poorly protected remote access.
The common thread is that this French supermarket cyber attack didn’t need anything clever. A reachable management interface, an unsupported device and a remote access route for a maintenance contractor are enough.
Where this lands for the sectors we work in
These are our own correlations, not findings from the incident:
- Critical National Infrastructure, energy and COMAH sites. Controllers that nobody has inventoried or checked for exposure. Where a process is temperature, pressure or flow dependent, the consequences go well beyond spoiled stock.
- Manufacturing. Plants run on a mix of old and new controllers. End-of-life kit that works perfectly well tends to stay in service for decades and the fridge story is partly a story about that.
- Maritime, rail and aviation. These sectors depend on third-party maintainers with remote access, often through vendor tools and gateways. That is exactly the exposure route CERT-FR highlights. Supply chain remote access deserves the same scrutiny as your own staff.
- Defence and government. The lesson is that safety-critical or mission-critical systems should be assumed reachable until proven otherwise and that “it isn’t connected” needs to be tested, not asserted.
- SMEs and enterprise. Not every business has OT, but most have building management, refrigeration, CCTV or access control on the network, often managed by a supplier. Those are the Danfoss-shaped risks of the corporate world.
What to do this week
- Find out what you have. Inventory every internet-facing system, including the ones a contractor installed years ago.
- Check whether management interfaces are reachable from the internet. If remote access is essential, restrict it to known IP addresses or put it behind a properly controlled gateway.
- Identify anything end of life, then plan its replacement or isolation. Patching won’t help if no patches exist.
- Review who has remote access and why. Ask your maintenance suppliers the same questions you ask yourself.
- Rotate credentials, remove shared accounts and check you can monitor and log OT connectivity.
- Rehearse the failure. Ask what you would do if your cooling, heating or process control started doing the wrong thing and whether anyone would notice in time.
- Register for the NCSC’s free Early Warning service.
The attackers in France didn’t need to defeat a clever defence. They found something that nobody had been looking at. The cheapest cyber security improvement most organisations can make right now is to go and look.
If you’d like a second pair of eyes on your OT exposure or supplier remote access, the Arcanum team is here to help. Get in touch.
Sources:
- CERT-FR alert CERTFR-2026-ALE-012
- Time: ‘Unprecedented’ Cyberattack Targets French Supermarket Fridges
- The Hacker News: Attackers Heat French Supermarket Fridges Up to 50°C by Hijacking Danfoss Controllers
- Claroty Team82: Danfoss refrigeration controller vulnerabilities
- Industrial Cyber: UK NCSC warns of increased OT targeting
- Trend Micro: Federal agencies warn of ongoing PLC exploitation